The Beacon 800 is a versatile, low-cost fixed system controller for one to eight points of gas detection. It is microprocessor controlled and is capable of accepting up to 8 separate 4-20 mA sensor transmitters, which can be either 2 or 3 wire. The Beacon 800 can be powered by either 24 Volt DC, or 85-264 Volt AC. It is simple to operate and comes complete with a wall mount installation kit. The 2 large digital displays have backlighting and easily identify both the gas type and the gas concentration for all 8 channels simultaneously. The Beacon 800 is housed in a NEMA 4X rated case for a weather tight seal. This case design complies with lock out / tag out standards and can be fully secured. An external reset switch allows alarms to be silenced from outside the controller housing. The bottom mounted wiring hubs allow for easy wiring. With 3 amp rated relays, the Beacon 800 can be wired directly to a variety of devices like alarm horns, buzzers, or lights. This eliminates the need for costly external relays from the controller to devices. RKI offers the industry's widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon 800, providing gas monitoring protection for almost any application.
Part No. 72-2108RK
Specifications
Conduit Connection: 3/4-Inch NPT Conduit Hubs (4 Provided) for Sensor, Power, & Relay Wiring
Wiring Termination: Screw Type Terminal Block, 14 Gauge Maximum
Display: Two LCD, Backlit
Inputs: 4-20 mA Transmitters
Sampling Method: Sample Draw Heads
Outputs: Programmable Form-C & Common Relays or 24 Volt DC Output
Alarm: Audible (94dB) & Visible
Operating Temperature: 14 F to 122 F (-10 C to 50 C)
Relative Humidity: 0 to 100% RH
Enclosure: NEMA-4X Non-Metallic, Waterproof, Chemical & Weather Resistant
Power: 85-264 Volt AC or 24 Volt DC Standard, Battery Backup Option Available